SPLIT TYPEROOM AIR CONDITIONERWALL MOUNTEDtypeModels Indoor unit Outdoor unitINVERTERSERVICEINSTRUCTIONR410AASU 9RLFASU12RLFASU15RLSAOU 9RLFWAOU12RLFW
7. LOUVER CONTROL1. VERTICAL LOUVER CONTROL2. SWING OPERATIONEach time the button is pressed, the air direction range will change as follow:(Function
8. COMPRESSOR CONTROL1. OPEARTION FREQUENCY RANGEThe operation frequency of the compressor is different based on the operation mode asshown in the tab
9. TIMER OPEARTION CONTROL1. OPEARTION FREQUENCY RANGEThe table11 shows the available timer setting based on the product model.ON TIMER / OFF TIMER PR
3. SLEEP TIMERIf the sleep is set, the room temperature is monitored and the operation is stopped automatically.If the operation mode or the set tempe
10. ELECTRONIC EXPANSION VALVE CONTROLThe most proper opening of the electronic expansion valve is calculated and controlled under thepresent operatin
15. MANUAL AUTO OPERATION (Indoor unit body operation)If MANUAL AUTO Button is set, the operation is controlled as shown in Table13.If the remote cont
20. DEFROST OPERATION CONTROL01-131. CONDITION OF STARTING THE DEFROST OPERATIONThe defrost operation starts as shown in the following Table 16.2. CON
01-14Outdoor fan : OFFCompressor speed:0rpsEEV : 480pulse4-way valve : OFFCompressor speed : 90rps (09/ 12)70rps (15)3. Defrost Flow ChartThe defrosti
21. OFF DEFROST OPEARTION CONTROL1. OFF DEFROST OPERATION CONDITIONWhen operation stops in the [Heating operation] mode, if frost is adhered to the ou
22. VARIOUS PROTECTIONS1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROLThe discharge gas thermosensor (discharge thermistor : Outdoor side) wi
CONTENTS1. DESCRIPTION OF EACH CONTROL OPERATION1. COOLING OPERATION...
3. ANTIFREEZING CONTROL (Cooling and Dry mode)The compressor frequency is decrease on cooling & dry mode when the indoor heat exchangertemperature
2 . TROUBLE SHOOTINGR410AWALL MOUNTED typeINVERTER
2. TROUBLESHOOTING02-012-1 ERROR DISPLAYWhen "Er" in Temperature Display is displayed, inspection of the air conditioning system is necessar
02-022. ERROR CODE HISTORY DISPLAYUp to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.1. Stop the a
02-031. ERROR DISPLAY2-1-3 INDOOR UNIT DISPLAYError contentsOperation lamp(Green)TroubleshootingTimer lamp(Orange)4 times flash1 times flash1 times fl
02-042-2 TROUBLE SHOOTING WITH ERROR CODETrouble shooting 1-1OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause:OKIndic
02-05Trouble shooting 1-2INDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause:OKIndicate or Display:YESYESNOOKSerial commu
Trouble shooting 2INDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause:Check Point 2 : Check Remote Control and Controller
Detective Actuators:Detective details:Forecast of Cause:Check Point 3 : Replace Controller PCBCheck Point 2 :Check Indoor unit electric componentsYESY
02-08Trouble shooting 4INDOOR UNITINDOOR UNIT Error Method:Indicate or Display:Detective Actuators:Detective details:Forecast of Cause :OKOKManual aut
1 . DESCRIPTION OF EACHCONTROL OPERATIONR410AWALL MOUNTED typeINVERTER
Trouble shooting 5INDOOR UNITINDOOR UNIT Error Method:Indicate or Display:Detective Actuators:Detective details:Forecast of Cause :Check Point 2 :Chec
Trouble shooting 6INDOOR UNITINDOOR UNIT Error Method:Indicate or Display:Detective Actuators:Detective details:Forecast of Cause :Check Point 2 :62.9
Trouble shooting 7INDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause:Check Point 1 : Check rotation of FanCheck Point 2
Detective Actuators:Detective details:Forecast of Cause:Check Point 2 : Replace Main PCBYESYESNOTrouble shooting 8OUTDOOR UNIT Error Method:Indicate o
Trouble shooting 9INDOOR UNITOUTDOOR UNIT Error Method:Indicate or Display:Detective Actuators:Detective details:Forecast of Cause :OKOKOKOKPFC circui
Trouble shooting 10OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause :Check Point 3 : Check Outdoor FanOKOKIndicate or
Trouble shooting 11INDOOR UNITOUTDOOR UNIT Error Method:Indicate or Display:Detective Actuators:Detective details:Forecast of Cause :Check Point 2 :Ch
Trouble shooting 12OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause :Check Point 2 :6.09.612.416.121.027.8Resistance
Trouble shooting 13OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause :Check Point 2 :26.935.246.662.384.2115.2Resistan
Trouble shooting 14OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause :Check Point 4 : Replace Main PCBYESNOOKIndicate
( Fig.1 : Limit of Maximum Frequency based on Outdoor Temperature )1. COOLING OPERATION1-1 COOLING CAPACITY CONTROLA sensor (room temperature thermist
Trouble shooting 15OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause :OKOKIndicate or Display:Check Point 2: Replace M
Trouble shooting 16OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause :Check Point 2 : Check connection of around the C
Trouble shooting 17OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause:Check Point 3 : Check Outdoor unit fan motorOKOKI
Trouble shooting 18INDOOR UNIT Error Method:Indicate or Display:Detective Actuators:Detective details:Forecast of Cause :OKOKOKOK4-way valve errorIndo
Trouble shooting 19INDOOR UNITOUTDOOR UNIT Error Method:Indicate or Display:Detective Actuators:Detective details:Forecast of Cause :Discharge tempera
Trouble shooting 20Forecast of Cause:OKOKIndoor Unit - No Power1. Power Supply failure 2. External cause3. Electrical Components defectiveCheck Point
Trouble shooting 21Forecast of Cause:Check Point 3 : Check Electrical ComponentsOKOKOKOKYESYESOKNOCheck Point 1 : Check Installation ConditionOutdoor
Trouble shooting 22Forecast of Cause:Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)Check Point 1 : Check indoor an
AttentionTrouble shooting 23Forecast of Cause:Check Point 2 : Check Outdoor Unit OperationCheck Point 1 : Check Indoor UnitCheck Point 3 : Check Site
Trouble shooting 24Forecast of Cause :Trouble shooting 25Forecast of Cause:OKOKOKOKOKOKOKOKOKOKMPa MPaAbnormal Noise1. Abnormal installation (Indoor/
2. HEATING OPERATION2-1 HEATING CAPACITY CONTROLA sensor (room temperature thermistor) built in the indoor unit body will usually perceivedifference o
SERVICE PARTS INFORMATION 1MPa MPaCompressorDiagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )Does not s
SERVICE PARTS INFORMATION 2Check Point 1 : Check ConnectionCheck Point 2 : Check Winding ResistanceCheck Point 3 : Replace Main PCBCSRInverter Compres
SERVICE PARTS INFORMATION 3Check Point 2 : Check Coil of EEVYellow - RedOrange - RedBlue - RedWhite - RedRead wire464Resistance valueCheck Point 1 : C
SERVICE PARTS INFORMATION 5Check Point 1 : Check rotation of FanOutdoor unit fan motorRotate the fan by hand when operation is off.(Check if fan is ca
3 . APPENDING DATAR410AWALL MOUNTED typeINVERTER
03-013-1. FUNCTION SETTINGFollow the instructions in the Local Setup Procedure, which is supplied with the remote control,in accordance with the insta
03-02( Factory setting)Setting DescriptionFunction Number Setting ValueYesNo400001( Factory setting)Setting DescriptionFunction Number Setting ValueNo
MIN.HEATMIN.HEATMIN.HEAT03-03Settings will not be changed if invalid numbers or setting values are selected.After the power is turned on, perform the
03-04(1) Press the MODE button for more then 5 seconds.(3) Press the MODE button. (Return to normal display)Custom code setting for remote controller(
-10.0 58.2 0.73-30.0 1131.9 0.21-5.0 44.0 0.93 -25.0 804.5 0.290.0 33.6 1.15 -20.0 579.6 0.405.0 25.9 1.39 -15.0 422.9 0.5310.0 20.2 1.66 -10.0 312.3
4. AUTO CHANGEOVER OPERATION01-03Operation flow chartSTARTRoom temp.Room temp.>Ts+4°F(2°C)?COOLING OPERATIONHEATING OPERATIONYESYESNONONONOYESYESTS
1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,JapanSep. 2010 Printed in Japan
5. INDOOR FAN CONTROLThe airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH,while the indoor fan only runs.When Fan mode is set at
The maximum value of the indoor fan speed is set as shown in Figure5, based on the detectedtemperature by the indoor heat exchanger sensor on heating
6. OUTDOOR FAN CONTROL( Table7 : Outdoor fan speed )*The outdoor fan speed mentioned above depends on the compressor frequency.(When the compressor fr